Guidance

Check your fire safety responsibilities under the Fire Safety (England) Regulations 2022 (accessible)

Updated 25 October 2023

Who’s responsible, Goverment Guide Lines.

If you are a Responsible Person on whom duties are imposed under the Fire Safety (England) Regulations (hereafter referred to as “the Regulations”), find out what your responsibilities are under the Regulations.  The commencement date of the Regulations is 23 January 2023.  The duties in these Regulations supplement those imposed by the Regulatory Reform (Fire Safety) Order 2005 (as amended).

From:  Home Office

Applies to England only

This information is not exhaustive but is designed to provide you with a high-level summary.

Who is this guidance for?

This guidance is for people who have responsibilities under the Fire Safety (England) Regulations 2022 (“the Regulations”).  You will have such responsibilities if, under the Regulatory Reform (Fire Safety) Order 2005 (“the Fire Safety Order”), you are a “Responsible Person” (or a person who has some responsibilities) on whom the Fire Safety Order imposes various duties in relation to fire safety in a residential building, such as a block of flats or student accommodation.

Check your fire safety responsibilities under the Fire Safety Order – GOV.UK (www.gov.uk).

Background to the Fire Safety (England) Regulations

In 2017, at Grenfell Tower, a high-rise block in West London, a tragic fire resulted in the deaths of 72 residents, the most serious loss of life in a single fire in the UK since World War 2.  The Government immediately ordered a Public Inquiry into the fire.

In October 2019, the Grenfell Tower Inquiry published the findings of Phase 1 of the Inquiry.  The findings included many important recommendations to prevent such a tragedy from ever happening again.  The Government undertook, in principle, to introduce new regulations that would bring the recommendations into force.  These regulations take the form of the Fire Safety (England) Regulations 2022 and extend duties imposed by the Regulatory Reform (Fire Safety) Order 2005.

To which buildings do the Fire Safety (England) Regulations apply?

These Regulations apply to all buildings in England that comprise two or more domestic premises (including the residential parts of mixed-use buildings) although there are more requirements depending on the height as explained in this guide.  These buildings are, principally, blocks of flats (whether purpose-built or converted from another type of building, such as a house or office building), but also include blocks used for student accommodation.

The Regulations apply regardless of whether the flats are subject to a long (e.g. 99 years) lease or are rented, and regardless of whether the flats are used to accommodate the general public or a particular group of people (as in the case of, for example, sheltered housing for older people).

The Fire Safety (England) Regulations impose duties on you if you are the Responsible Person for any building which:

  • contains two or more sets of domestic premises
  • contains common parts through which residents would need to evacuate in the case of an emergency

The Regulations apply to:

  • parts of the building that are used in common by the residents of two or more domestic premises (e.g. communal corridors and stairways)
  • flat entrance doors
  • the walls and floors that separate any domestic premises from other domestic premises, plant rooms, etc, or from parts of the building that are used in common by the occupants of two or more domestic premises
  • plant rooms and other non-domestic areas of the building, such as tenant halls, offices, laundries, gymnasia and commercial premises
  • external walls of the building, including doors or windows within an external wall, and attachments to an external wall (e.g. balconies).

The Regulations do not apply within individual flats, other than in respect of measures installed within flats for the safety of other residents of the building (e.g. sprinklers, smoke detectors connected to a communal fire alarm system, etc).

Enforcement of the Regulations is the responsibility of the same enforcing authority as enforces the Regulatory Reform (Fire Safety) Order 2005.  In the case of a block of flats, this is virtually always the local fire and rescue authority.

Do the Regulations only apply to high-rise residential buildings?

The sections that follow begin with requirements that apply to all residential buildings.  There then follow requirements that apply only to buildings of greater than 11m in height.  Finally, the guidance sets out requirements that apply only to high-rise residential buildings.  The section headings make it clear whether the section applies to all residential buildings, only to buildings of greater than 11m in height, or only to high-rise residential buildings.

Because Grenfell Tower was a high-rise block, much of the focus of the recommendations of the Public Inquiry was concerned with measures to ensure the safety of residents in high-rise blocks of flats.  However, the Government is determined to ensure that residents of all residential buildings are as safe as possible from fire and that they feel safe from fire.

What is a high-rise residential building?

For the purpose of the Regulations, a residential building is to be considered as high-rise if either of the following circumstances apply:

  • the building is at least 18 metres above ground level, measured from the lowest ground level adjoining the outside of the building to the height of the floor in the top storey (ignoring any top storey that contains only plant or machinery); or
  • the building is seven storeys or more, excluding any storeys below ground level).

A mezzanine floor is to be treated as a storey if its floor area is at least 50% of the floor area of the largest storey in the building which is not below ground level.

Responsible Persons

It is the Fire Safety Order that defines the meaning of Responsible Person in the context of both the Order and the Fire Safety (England) Regulations.

As the term “Responsible Person” has a legal definition, it is not open to building owners, enforcing authorities or others to choose to “make” someone the Responsible Person, nor can the responsibility for compliance with either the Fire Safety Order or the Fire Safety (England) Regulations be delegated to others (though the Responsible Person will normally need to engage other parties, such as contractors, to assist them in compliance).

Under certain circumstances, duties can also fall on individuals other than the Responsible Person if any of the requirements of the Fire Safety Order relate to matters within their control.  In such circumstances, the Responsible Person will still also retain their duties under the Fire Safety Order.

For all practical purposes, in the case of a block of flats, the Responsible Person will be the person who has control of the premises in connection with carrying on a business.  This will, typically, be the freeholder or the managing agents for the block, or, for example, a residents’ management company.

If any part of the building is a workplace, the employer of persons employed to work in that workplace will be a Responsible Person.  This can occur if, for example, a concierge is employed or parts of the building are used for commercial purposes.

So, there may be circumstances in which there is more than one Responsible Person within the same building.  However, even in these circumstances, overall control of the building most commonly rests with the freeholder, managing agents or a residents’ management company.

Sometimes, confusion arises from the term “Person”, because it might be expected that the “Responsible Person” is an individual living person (or what, in law, is described as a “natural person”). However, commonly, the Responsible Person will be an organisation, such as a property company or firm of managing agents (or what, in law, is described as a “legal person”).

If you are unclear as to whether you are the Responsible Person for the purpose of the Fire Safety (England) Regulations, or otherwise are unsure as to the correct identity of the Responsible Person, you should seek legal advice. It is not the role of, for example, the fire and rescue service to advise you in this respect, though, in enforcing the Regulations, the fire and rescue service may require to be informed as to the identity of the Responsible Person.

Duties of the Responsible Person (General)

Information to residents

You must display fire safety instructions in a conspicuous part of the building.  The instructions must be in a comprehensible form that residents can reasonably be expected to understand.

The instructions must cover the following matters:

  • the evacuation strategy for the building (e.g. stay put or simultaneous evacuation)
  • instructions on how to report a fire (e.g. use of 999 or 112, the correct address to give to the fire and rescue service, etc.)
  • any other instruction that tells residents what they must do when a fire has occurred

These instructions must also be provided directly to new residents as soon as reasonably practicable after they move into their accommodation, as should also be the case if there are any material changes to the instructions (e.g. as a result of alterations to the building).  In addition, these instructions should be reissued to all existing residents at periods not exceeding 12 months.

You must also provide relevant information about fire doors, particularly residents’ flat entrance doors, as these play an important part in containing any fire within the flat in which it starts.  In particular, you must provide information to all residents to the effect that:

  • fire doors should be shut when not in use
  • residents or their guests should not tamper with self-closing devices on fire doors
  • residents should report any fault with, or damage to, fire doors immediately to the Responsible Person

Again, the information about fire doors must be provided to residents as soon as reasonably practicable after they move into their flat and at periods not exceeding 12 months thereafter.

Duties of the Responsible Person (Buildings over 11m in height)

If you are the Responsible Person for a building which contains two or more sets of domestic premises and is above 11m in height (typically a building of five storeys or more), the Fire Safety (England) Regulations impose additional duties to those described above.  For the purpose of these duties, the height of the building should be measured as described (PDF, 4.18MB).

These additional duties are set out below.

Fire Doors are crucial in preventing the spread fire and smoke in buildings.

The Fire Safety Act 2021 clarified that flat entrance doors must be considered in the Fire Risk Assessment mandated by the Fire Safety Order. The Fire Safety (England) Regulations 2022 require regular checks to ensure that self-closing devices are working and the fire doors including flat entrance doors are in efficient working order and in good repair. These checks are to ensure that the existing door standard is maintained.

During the fire risk assessment, the assessor may recommend improvements to be made to the door and it will be for the Responsible Persons to determine how these are implemented. If faults are found with the doors, then it may be necessary to undertake appropriate maintenance to ensure they remain fit for purpose or, where needed, to replace them. However, there is no requirement to replace a fire door simply because it does not meet the current standard under Building Regulations if the door remains in full working order from a fire safety point of view.

Fire door checks (Communal areas)

All fire doors in communal areas of the building must be checked at least every three months.  Typically, these doors will include:

  • doors to stairways and stairway lobbies
  • cross-corridor doors, which sub-divide corridors
  • doors to storage and electrical equipment cupboards
  • doors to riser shafts, within which various services run

In checking these doors, you must ensure that the doors are effectively self-closing (or, in the case of cupboard and riser doors, are kept locked shut).  Self-closing doors should fully close into their frames when the doors are opened at any angle and released.

A simple way to check this is to:

  • firstly, open the door fully, then let it go
  • then open the door to around 15 degrees and let it go

In both cases, the door should fully close into the frame, overcoming the resistance of any latch or friction with the floor.

You should also check that doors, frames and any glazing are undamaged and that any intumescent strips and smoke seals (where provided) are also undamaged.

Defects in the doors, frames and self-closing devices should be rectified as soon as reasonably practicable.

It is not intended that these checks should involve any more detailed, technical examination of the doors, or of the original standard of installation, nor is it intended that these checks need to be carried out by specialists.  It is expected that the Responsible Person, or their staff, should, with simple instruction, be able to carry out the checks. 

Flat entrance door checks

You must use best endeavours to undertake checks of all flat entrance fire doors at periods not exceeding 12 months.

You must keep a record of the steps taken to comply with this requirement, including, in any case where access to a flat was not granted for this purpose during any 12-month period, the steps taken to try to gain access.

In checking these doors, you must ensure that the doors are effectively self-closing.  The doors should fully close into their frames when the doors are opened at any angle and released, overcoming the resistance of any latch on the door.  A simple way to perform this check is described above for communal area doors.

You should also check that doors, frames and any glazing are undamaged (and that glazing has not, obviously, been replaced with glazing that might not be fire-resisting), and that any intumescent strips and smoke seals (where provided) are also undamaged.

Defects in the doors, frames and self-closing devices should be rectified as soon as reasonably practicable and depending on the risks identified.

It is not intended that these checks should involve any more detailed, technical examination of the doors, or of the original standard of installation, nor is it intended that these checks need to be carried out by specialists.  It is expected that the Responsible Person, or their staff, should, with simple instruction, be able to carry out the checks. 

In the case of any leasehold flats, arrangements will need to be made with the leaseholders to grant access to their flats for the purpose of flat entrance door checks.  In the event of an impasse, a court order can be obtained for this purpose.  It is recommended that any new leases include this right of access.

Where inspections identify the need for repair or replacement of any fire door (e.g. communal or flat entrance door), this work must be undertaken by a competent contractor as soon as reasonably practicable.

The Fire Safety Regulations 2022 do not specify requirements for the fire resistance of the doors. The Regulations make no change to the required fire performance of flat entrance doors; this continues to be a matter for the fire risk assessment carried out for compliance with Article 9 of the Fire Safety Order and applicable guidance.

It is stressed that the purpose of the fire doors checks under Regulations 10(4) and (6) is primarily to ensure that self-closing devices are working, and the flat entrance doors are in good working order from a fire safety point of view, while also checking that there are no visually obvious faults signs of tampering, defects or changes to the doors provided.

Guidance on the fire performance of the doors continues to be available in the Fire Safety in Purpose-Built Blocks of Flats guide.

The guidance advises that a fire risk assessor might determine, according to risk, original flat entrance doors that would not meet the current standard for 30 minutes’ fire resistance and might not be fitted with intumescent strips and smoke seals, should either be replaced, upgraded or simply left in situ.

In particular, the guidance advises that ‘notional’ FD30 doors, which satisfied earlier standards for flat entrance doors, will usually continue to be acceptable for compliance with the Fire Safety Order unless there is a need to improve their fire performance to compensate for a specific building design, or shortcomings in other fire precautions.

Duties of the Responsible Person (High-rise buildings)

If you are the Responsible Person for a high-rise residential building which contains two or more sets of domestic premises, the Fire Safety (England) Regulations impose further additional duties to those described above.  These further additional duties are set out below.

There are a few requirements for premises of this height that require information to be sent electronically to your local fire and rescue service. The National Fire Chiefs Council (NFCC) can signpost you to your local service. In addition, it will have information on what type of file size and format they can take, and what email address to use.

Wayfinding signage

Because of the height of the building, there is a need to provide suitable signage to assist fire and rescue service crews with orientation in the event of a fire. (If the building was designed after November 2020, the appropriate signage should already have been incorporated within the building for compliance with the Building Regulations.)

The principles that apply to this signage are as follows:

  • When firefighters reach the landing of any stairway, there should be signage that clearly indicates to them the floor number on which they are located and the flat numbers on that floor.
  • When firefighters use a lift designed for their use to reach floors, the same signage should be clearly visible to them when the lift doors open.
  • The signs must be visible both in normal conditions and in low lighting or smoky conditions.

Read a detailed specification for these signs (PDF, 4.18MB), including the size of the lettering, the typeface to be used, the mounting height and suitable wording.

You must make sure that the signs are maintained in good condition, so it is important that you check them regularly (e.g. during other legally required checks within the building).

Secure information box

In the event of a fire in any high-rise residential building, it is important that certain information is readily available for the fire and rescue service.

The Fire Safety (England) Regulations require that the information is held in a secure information box, which must be positioned at a location in or on the building that is readily accessible to the fire and rescue service. The box must be capable of containing the documents required by these Regulations, and it must be reasonably secure from unauthorised access and vandalism.

You must provide the local fire and rescue service with the details necessary to access the secure information box and must inform the fire and rescue service as soon as practicable if there are any changes to these details.  Typically, a secure information box is protected against unauthorised access by means of a lock that is openable only with a key that is legally protected from copying and that is carried on fire and rescue service appliances.  However, other alternative means of securing the box might be acceptable to the local fire and rescue service, with whom there should be some discussion prior to adopting an alternative.

For the purposes of these Regulations, your secure information box must contain:

  • the name, address and telephone number within the United Kingdom of the Responsible Person
  • the name and contact information of such other persons within the United Kingdom as are provided with facilities to, and are permitted to, access the building on behalf of the Responsible Person
  • a copy of the floor plans and building plan

You must inspect the secure information box at least annually to ensure that it remains secure and accessible to the fire and rescue service. It is strongly recommended that you also ensure that the information within the box remains accurate.

Good practice can be found on the provision of secure information boxes in high-rise residential buildings.

While it contains useful guidelines for example on the appropriate positioning on boxes, it proposes a higher specification of security of the box than is required by the Regulations.

Information on external wall construction

You must prepare a record of the design of the external walls of the building, including details of the materials from which they are constructed. You must provide this record to the local fire and rescue service by electronic means.

This record must identify the level of risk to which the design and materials of the external walls gives rise, as determined by the fire risk assessment that you are required by the Fire Safety Order to carry out. You must also record any mitigating steps that have been taken in respect of that risk.

Other than in blocks of flats with external walls of traditional masonry construction, unless the above information is readily available and known to be reasonably accurate, determining the information required by the Fire Safety (England) Regulations will normally require special skills, not normally held by a typical fire risk assessor engaged to carry out the fire risk assessment required by the Fire Safety Order.  Where necessary, you must seek the advice and assistance of someone with sufficient training and experience/knowledge.  You will, however, remain responsible for compliance with the Regulations.

In the case of external wall construction that is known to be of traditional masonry construction, it might be reasonable to assume that the risk of external fire spread is acceptable without further investigation, in which case this should be recorded within the record provided to the fire and rescue service.  However, even in the case of low- risk, traditional masonry construction, if there are attachments (such as balconies or decorative cladding) that, because of their combustibility, might result in rapid external fire spread, further appraisal by a specialist is likely to be necessary.

The purpose of providing this information to the fire and rescue service is to assist them with operational pre-planning and to provide information that will be of value to front line crews at the time of a fire.

Accordingly, the information should be presented in a form, and be restricted to high-level detail, that is of practical value for this purpose; over-elaborate detail of construction, without any explanation of the implications in respect of fire performance and risk, may not be of practical value.

On the other hand, it is unlikely that simple identification of materials used in the external walls, whether combustible or not, will always help the fire and rescue service.

Typically, other than in the case of low-risk, traditional masonry construction, the information that should be provided will comprise the following:

  • an overview of the design of the external wall
  • brief information on the materials of construction, insulation and any cladding
  • any known defects in the construction (either as originally built or currently)
  • the level of risk presented by the external walls, cladding and any attachments (as determined, where necessary, by an appraisal carried out by specialists)
  • any mitigating steps that have been taken in relation to the risk as identified in the fire risk assessment

A code of practice for fire risk appraisal of external wall construction and cladding is published by the British Standards Institution as PAS 9980.

A suitable template for recording the information must be provided electronically to the fire and rescue service.

If any significant changes are made to the external walls of the building, the record described above must be revised, and the revised version must be provided to the fire and rescue service.

Floor plans and building plan

In addition, you must provide the fire and rescue service with a copy of these plans by electronic means, for example by email.

In the event of a fire in a high-rise building, plans of the building are of great assistance to fire and rescue service crews.  Accordingly, the Fire Safety (England) Regulations require that you must prepare a plan for each floor of a high-rise residential building.

An exception to the above is that, if the plans for each floor would be the same in all material respects, you can prepare just one single plan for those floors, provided the plan clearly indicates the floors to which it relates.

The floor plans must, together, identify the location of all lifts (identifying any designed for use by firefighters or for evacuation) and key fire-fighting equipment in the building including rising mains, smoke control systems and fire suppression systems.

In addition, you must prepare a single-page building plan, which shows the following:

  • the environs of the building (e.g. the building and its immediate surroundings)
  • details of the use of the building, for example for commercial or residential purposes
  • access for fire and rescue appliances
  • the dimensions of the building
  • information on the number of storeys of the building and the number of basement levels (if any)
  • information regarding the presence of maisonettes or scissor section flats
  • inlets for dry rising mains
  • inlets for wet rising mains
  • the location of shut-off controls for any sprinkler systems
  • access points for the building
  • the location of the secure information box
  • the location of the central controls for any smoke control system
  • the location of any firefighting shaft
  • the location of main stairways in the building
  • the location of the controls for any evacuation alert system

You must place a hard copy of the floor plans and the building plan in the secure information box. In addition, you must provide the local fire and rescue service with a copy of these plans by electronic means (i.e. email).

If any changes are made to the layout of the building or the location of the key fire‑fighting equipment described above, you must update the floor plans and building plan as soon as reasonably practicable after the changes are made.  You will then need to update the plans provided to the fire and rescue service by electronic means.

Lifts and essential fire-fighting equipment

In high-rise residential buildings, one or more lifts are designed to be used by fire and rescue service crews to reach upper floors during a fire.  In addition, there are other systems and equipment that will be used by the crews, such as rising mains (i.e. dry or wet risers) by which the crews obtain water on upper floors.

In addition, high-rise residential buildings normally incorporate other special fire safety measures on which the safety of both residents and firefighters may depend.  An example is a smoke control system that is intended to limit the passage of smoke into any stairway by removing smoke from common corridors and lobbies.  These systems are commonly, in turn, operated by a fire detection system.

In some high-rise residential buildings, there may be other systems or equipment that are provided for fire and rescue service use, such as evacuation alert systems, by which the fire and rescue service can operate special evacuation alert sounders within flats.

It is essential that all of these systems which are present operate correctly in the event of fire. Accordingly, the Regulations make requirements regarding routine checking of all such systems and equipment.  These checks are in addition to the servicing and maintenance of the systems (usually by a contractor) required by the Fire Safety Order.

You must undertake monthly routine checks of all lifts that are intended for use by firefighters.  Similarly, you must undertake monthly checks of any evacuation lifts that are provided for the evacuation of disabled people in the event of fire.

You must also undertake monthly checks of the following:

  • rising mains
  • smoke control systems
  • fire suppression systems
  • fire detection and fire alarm systems, including any systems linked to other fire safety equipment, such as smoke control systems
  • evacuation alert systems (a visual check of the control and indicating equipment, but not testing of the system)
  • automatic door opening or closing systems linked to fire detection and fire alarm systems

You must keep records of all of these monthly checks.  The records of these checks must be accessible to residents of the building.

If any of these checks reveal a fault in one of the above systems or equipment, you must take steps the rectify the fault.  If the fault cannot be rectified within 24 hours of its discovery, you must, as soon as reasonably practicable, notify the local fire and rescue service by electronic means.  You must also then inform them by electronic means when the fault has been rectified.

NFCC has developed templates for reporting faults and rectifications that can be used to send this information to your local fire and rescue service. Many fire and rescue services would prefer you to use these templates as it helps them process the information in a way that is useful for operational colleagues.

Responsible persons should consider the impact of the fault (e.g. the impact of smoke control system failure on means of escape) and the need for any consequent mitigation measures. Responsible persons should also consider the need to review the fire risk assessment for the building, particularly in the case of faults that will be of a prolonged nature.  Consideration should also be given to any potential impact on evacuation arrangements (e.g. in the event of failure of an evacuation lift). The need for continued compliance with duties under the Fire Safety Order should be taken into account.

It is not envisaged that any of the above checks will need to be carried out by specialists or contractors (though some Responsible Persons may choose to have the checks carried out by maintenance contractors that carry out other routine maintenance checks on a monthly, or more frequent, basis).  The checks required generally involve only visual inspection or simple functional operating checks.

However, the routine checks must confirm that the system or equipment is in efficient working order and in good repair, based on guidance for routine checks provided by the relevant industry standard or any recommendations made by the manufacturers of equipment within an operators’ manual.

The following are examples of the types of checks you will likely carry out for the above requirements but do make sure you refer to any operator’s manual for specifics about your equipment:

Lifts

The monthly check will involve operation of the firefighters’ switch (or evacuation lift switch) to ensure that it causes the lift to return to the fire and rescue service access (or evacuation) level, after which it can be operated only by the controls within the car.  It should then be ensured that these controls enable the lift to be taken to an upper floor, on which the doors can then be opened and closed from within the car.  You should also ensure, by means of a random check, that the landing controls are disabled and cannot call the lift to the floor in question.

Smoke control systems

Typically all that is required is to carry out one test each month to ensure that the smoke control system is capable of responding to a signal from any associated fire detection and fire alarm system.  Additionally, it should respond to operation of any manual control provided for use by the fire and rescue service.  Similarly, in the case of fire doors that are normally held open but close automatically on operation of a fire detection system (which are not common in blocks of flats), the monthly check will simply confirm that the doors do close on operation of the system.

Other systems and equipment

Normally it will be sufficient to carry out a visual check to ensure that the systems and equipment are undamaged and have not been subject to interference.  For example, this would apply in the case of the inlet and the landing valves of rising mains and the control valves of fire suppression systems.

Evacuation alert systems

No routine tests should be carried out; the system should only be tested at the time of routine maintenance (e.g. by a contractor).  The monthly check only involves a visual examination of the enclosure for the system control and indicating equipment to ensure that it has not been damaged or, for example, subjected to vandalism.

Call us on: 0121 525 1976

Fire Services Central Ltd

TrustScore 4.5 out of 5

4.7

We’d love To Do Business With You!

Contact us for your Fire Safety Requirments

We offer a nationwide service on fire extinguisher servicing, fire alarm servicing, fire extinguisher installation and fire alarm installation.

Head Office: Unit 25 Izons Ind Est,Oldbury Road,Birmingham B70 9BS.
Phone: 0121 525 1976
Email: info@fire.uk.net

Please fill out the form and one of our team will be in touch with you promptly. Thank you for your interest.

Phone:0121 525 1976 email: info@fire.uk.net

    Your Name (required)

    Your Email (required)

    Your Tel No (required)

    Site Post code

    How can we help you (required)